Add to Cart
IFM Continuous level sensor (guided wave radar) LR2050 LR0000B-ER34AKSKG/US
Okay, let's take a look at the details of the IFM Continuous Level Sensor (Guided Wave Radar) LR2050 LR0000B-ER34AKSKG/US:
1. Product Name:
- IFM Continuous Level Sensor (Guided Wave Radar) LR2050 LR0000B-ER34AKSKG/US
2. Description:
- The LR2050 LR0000B-ER34AKSKG/US is a continuous level sensor from IFM Electronics that uses guided wave radar technology.
- Guided wave radar level sensors are used to provide continuous measurement of the level of liquids, slurries, and solids in industrial applications.
3. Key Features:
- Guided wave radar technology for accurate and reliable level measurement
- Stainless steel housing and process connection for use in harsh environments
- 4-20 mA analog output and HART communication protocol
- Compact and easy to install design
- Protection rating of IP68/IP69K for submerged and high-pressure applications
4. Applications:
- The IFM LR2050 LR0000B-ER34AKSKG/US guided wave radar level sensor is suitable for a wide range of industrial applications, such as:
- Level measurement in storage tanks, silos, and process vessels
- Continuous monitoring of liquid and solid levels
- Process control and optimization in the food, chemical, and oil and gas industries
5. Connectivity:
- The sensor has a 4-wire DC connection:
- 1 x Brown (L+)
- 1 x Blue (L-)
- 1 x Black (4-20 mA analog output)
- 1 x White (HART communication)
- The sensor can be easily integrated into industrial control systems and automation networks.
6. Capabilities:
- Guided wave radar technology for accurate and reliable level measurement
- Stainless steel housing and process connection for use in harsh environments
- 4-20 mA analog output and HART communication protocol for integration with control systems
- Compact and easy to install design with IP68/IP69K protection rating
7. Compatibility:
- The IFM LR2050 LR0000B-ER34AKSKG/US guided wave radar level sensor is designed to be compatible with a wide range of industrial automation and control systems.
- It can be integrated with programmable logic controllers (PLCs), SCADA systems, and other industrial control equipment.
The LR2050 LR0000B-ER34AKSKG/US is a versatile and reliable continuous level sensor from IFM Electronics, using guided wave radar technology to provide accurate and reliable level measurement in a variety of industrial applications. Its stainless steel housing, 4-20 mA analog output, and HART communication capabilities make it suitable for use in harsh environments and easy integration with industrial control systems.
If you have any further questions about the IFM LR2050 LR0000B-ER34AKSKG/US guided wave radar level sensor or need additional information, please don't hesitate to ask.
Product characteristics
Number of inputs and outputs | Number of digital outputs: 1; Number of analogue outputs: 1 |
Probe length L [mm] | 150...2000 |
Process connection | threaded connection G 3/4 external thread |
Application
Special feature | Gold-plated contacts |
Application | for industrial applications |
Media | Liquids |
Dielectric constant of the medium | ≥ 1,8; (for media with a dielectric constant of 1.8...5 (e.g. oils), a coaxial pipe is needed for operation) |
Recommended media | water; hydrous media; oils; oil-based media |
Process temperature [°C] | -20...100; (see note under remarks) |
Pressure rating [bar] | 16 |
Vacuum resistance [mbar] | -1000 |
MAWP (for applications according to CRN) [bar] | 16 |
Electrical data
Operating voltage [V] | 18...30 DC |
Current consumption [mA] | < 50 |
Protection class | III |
Reverse polarity protection | yes |
Power-on delay time [s] | < 3 |
Measuring principle | guided wave radar |
Inputs / outputs
Number of inputs and outputs | Number of digital outputs: 1; Number of analogue outputs: 1 |
Outputs
Total number of outputs | 2 |
Output signal | switching signal; analogue signal; IO-Link |
Electrical design | PNP/NPN |
Number of digital outputs | 1 |
Output function | normally open / normally closed; (parameterisable) |
Max. voltage drop switching output DC [V] | 2.5 |
Permanent current rating of switching output DC [mA] | 150; (200 (...60 °C)) |
Number of analogue outputs | 1 |
Analogue current output [mA] | 4...20, invertible; (scalable) |
Max. load [Ω] | 500 |
Short-circuit protection | yes |
Type of short-circuit protection | pulsed |
Overload protection | yes |
Measuring/setting range
Probe length L [mm] | 150...2000 |
Active range A [mm] | L-40 (L-60); (when set to oil and oil based media) |
Inactive range I1 / I2 [mm] | 30 / 10 (30); (when set to oil and oil based media) |
Sampling rate [Hz] | 4 |
Setting range
Set point SP [mm] | 15...L-30 | |
Note on setpoint SP |
| |
Reset point rP [mm] | 10... L-35 | |
Note on reset point rP |
| |
In steps of [mm] | 1 | |
Hysteresis [mm] | > 5 |
Accuracy / deviations
Measuring error [mm] | ± 7 |
Offset error [mm] | 5 |
Resolution [mm] | 1 |
Zero signal (current) [mA] | 4.0 |
Full signal (current) [mA] | 20 |
Temperature drift per 10 K | ± 0.2 % |