Add to Cart
IFM Flow monitor SI6800 SIR11ABBFPKG/US-100-IPF
The IFM SI6800 SIR11ABBFPKG/US-100-IPF is a flow monitor. Here's some information about the monitor:
1. Model: SI6800 SIR11ABBFPKG/US-100-IPF
2. Manufacturer: IFM Electronic GmbH
3. Function: The flow monitor is designed to measure and monitor the flow rate of a liquid or gas in a pipeline or system. It provides real-time information about the flow rate and can trigger alarms or control actions based on predetermined thresholds.
4. Flow Measurement Principle: The specific flow measurement principle utilized by this monitor is not explicitly mentioned in the model number. It could be based on technologies such as thermal, ultrasonic, or vortex, among others. For accurate information about the flow measurement principle used in this model, it's recommended to consult the product documentation or datasheet.
5. Electrical Connection: The monitor supports a specific electrical connection type, indicated by the "/US-100-IPF" in the model name. The "/US" may represent a connector or electrical connection type compatible with the US market, while the "-100-IPF" may indicate additional details regarding the electrical connection or functionality. For precise information, it's best to refer to the product documentation or datasheet.
6. Housing Type: The monitor likely features a robust housing suitable for industrial environments. The specific details of the housing type or design are not evident from the provided model number.
For detailed specifications, installation guidelines, and compatibility information for the IFM SI6800 SIR11ABBFPKG/US-100-IPF flow monitor, it is recommended to consult the official documentation provided by IFM Electronic GmbH or contact their technical support. They will provide you with accurate and up-to-date information based on your specific requirements and the latest product information available.
Product characteristics
Number of inputs and outputs | Number of digital outputs: 1 |
Process connection | G 1 Aseptoflex Vario |
Application
Special feature | Gold-plated contacts |
Application | hygienic systems |
Medium temperature [°C] | -25...95; (for SIP process: ...140 °C) |
Pressure rating [bar] | 30 |
MAWP (for applications according to CRN) [bar] | 30 |
Electrical data
Operating voltage [V] | 19...36 DC |
Current consumption [mA] | < 60 |
Protection class | III |
Reverse polarity protection | yes |
Power-on delay time [s] | 10 |
Inputs / outputs
Number of inputs and outputs | Number of digital outputs: 1 |
Outputs
Total number of outputs | 1 |
Output signal | switching signal |
Electrical design | PNP |
Number of digital outputs | 1 |
Output function | normally open / normally closed; (parameterisable) |
Max. voltage drop switching output DC [V] | 2.5 |
Permanent current rating of switching output DC [mA] | 250 |
Short-circuit protection | yes |
Type of short-circuit protection | pulsed |
Overload protection | yes |
Measuring/setting range
Probe length L [mm] | 55 |
Liquids
Setting range [cm/s] | 3...300 |
Greatest sensitivity [cm/s] | 3...100 |
Gases
Setting range [cm/s] | 200...3000 |
Greatest sensitivity [cm/s] | 200...800 |
Accuracy / deviations
Repeatability [cm/s] | 1...5 | ||
Note on repeatability |
| ||
Temperature drift [cm/s x 1/K] | 0.1; (for water 5...100 cm/s; 10...70 °C) | ||
Temperature gradient [K/min] | 300 | ||
Switch point accuracy [cm/s] | ± 2...± 10; (for water 5...100 cm/s; 25 °C; Factory setting) | ||
Hysteresis [cm/s] | 2...5; (for water 5...100 cm/s; 25 °C; Factory setting) |