Add to Cart
IFM Pressure switch with IO-Link PV7003 PV-025-SEG14-UFRVG/US/ /
The IFM PV7003 PV-025-SEG14-UFRVG/US/P is a pressure switch with IO-Link functionality. Here's some information about the pressure switch:
1. Model: PV7003 PV-025-SEG14-UFRVG/US/P
2. Manufacturer: IFM Electronic GmbH
3. Function: The pressure switch is designed to monitor and control the pressure of a fluid in a system or process. It allows for the detection of specific pressure thresholds and can trigger actions or signals based on those thresholds.
4. Pressure Measurement Range: The specific pressure measurement range of the switch depends on the model variant. Unfortunately, the provided model number does not contain information about the pressure range. It's recommended to refer to the product documentation or datasheet for the exact pressure measurement range of this particular model.
5. IO-Link Functionality: The pressure switch is equipped with IO-Link, which is a communication protocol that allows for bi-directional communication between the switch and a controller or other devices. IO-Link enables enhanced configuration, monitoring, and diagnostics capabilities for the pressure switch.
6. Electrical Connection: The switch supports a specific electrical connection type, indicated by the "/US/P" in the model name. The "/US" may represent a connector or electrical connection type compatible with the US market, while the "/P" could indicate additional details regarding the electrical connection or functionality. For precise information, it's best to consult the product documentation or datasheet.
7. Housing Type: The pressure switch is likely housed in a robust enclosure suitable for industrial environments. The specific details of the housing type or design are not evident from the provided model number.
For detailed specifications, installation guidelines, and compatibility information for the IFM PV7003 PV-025-SEG14-UFRVG/US/P pressure switch with IO-Link functionality, it is recommended to consult the official documentation provided by IFM Electronic GmbH or contact their technical support. They will be able to provide you with accurate and up-to-date information based on your specific requirements and the latest product information available.
Product characteristics
Number of inputs and outputs | Number of digital outputs: 2 | |||
Measuring range |
| |||
Process connection | threaded connection G 1/4 external thread (DIN EN ISO 1179-2); internal thread:M5 |
Application
Measuring element | metallic thin film cell | |||
Application | for industrial applications | |||
Media | liquids and gases | |||
Medium temperature [°C] | -40...90 | |||
Min. bursting pressure |
| |||
Pressure rating |
| |||
Note on pressure rating |
| |||
Vacuum resistance [mbar] | -1000 | |||
Type of pressure | relative pressure; vacuum |
Electrical data
Operating voltage [V] | 18...30 DC |
Current consumption [mA] | < 15 |
Min. insulation resistance [MΩ] | 100; (500 V DC) |
Protection class | III |
Reverse polarity protection | yes |
Power-on delay time [s] | < 0.3 |
Inputs / outputs
Number of inputs and outputs | Number of digital outputs: 2 |
Outputs
Total number of outputs | 2 |
Output signal | switching signal; IO-Link; (configurable) |
Electrical design | PNP/NPN |
Number of digital outputs | 2 |
Output function | normally open / normally closed; (parameterisable) |
Max. voltage drop switching output DC [V] | 2 |
Permanent current rating of switching output DC [mA] | 100 |
Switching frequency DC [Hz] | < 170 |
Short-circuit protection | yes |
Type of short-circuit protection | pulsed |
Overload protection | yes |
Measuring/setting range
Measuring range |
| ||||||||||||
Set point SP |
| ||||||||||||
Reset point rP |
| ||||||||||||
In steps of |
| ||||||||||||
Factory setting |
|
Accuracy / deviations
Switch point accuracy [% of the span] | < ± 0,5 (nach DIN EN 61298-2) |
Repeatability [% of the span] | < ± 0,05; (with temperature fluctuations < 10 K) |
Characteristics deviation [% of the span] | < ± 0,5; (linearity incl. hysteresis and repeatability, limit value setting to DIN EN IEC 62828-1) |
Linearity deviation [% of the span] | < ± 0,1 (BFSL) / < ± 0,2 (LS) |
Hysteresis deviation [% of the span] | < ± 0,2 |
Long-term stability [% of the span] | < ± 0,1; (per 6 months) |
Temperature coefficient zero point [% of the span / 10 K] | < 0,1 (-25...90 °C) / < 0,2 (-40...-25 °C) |
Temperature coefficient span [% of the span / 10 K] | < 0,1 (-25...90 °C) / < 0,2 (-40...-25 °C) |